2025 Mechanical Electrical Engineering Consultancy Services for St Bridget's Girls National School Cabinteely Dublin 18
Description du marché
The Fire Alarm and Detection System CAT 01 LIFE SAFETY Fire panel location Not Compliant System Level of Detection Cover Not compliant The current level of detection cover will not meet L4 or L3, parts of escape routes are not covered, rooms have no detection. Detection not installed in accordance with the standards. Final exits with no detection. System Sound Level Not compliant. Condition and health of system Not compliant. The fire alarm installation is over ten years old, There are smoke detector over 30 years old, the cabling type of the original installation is not known, the cabling at the fire alarm panel is not original.